SEQUENCE OF OPERATION
This water heater has two distinct electrical systems. One system, referred to as the “Control Circuit”, controls the
w
ater heater operation, while the other system referred to as the “Power Circuit”, connects the electrical power to the
heating elements, The electrical contactors interconnect these two systems. In order to clearly illustrate the electrical
circuits, two wiring diagrams are provided. These diagrams are labeled as the “Control Circuit Wiring Diagram” and the
Power Circuit Wiring Diagram” and they are attached to the surface of the panels inside the water heater control
cabinet.
The control circuit operates with 120VAC electrical service. This voltage is provide by the multi-tap transformer which
has the primary coil connected to the field wiring that is serving the water heater. The Transformer, Thermostat, Hi-Limit
c
ontrol, and the Contactor Coil are always included in the Control Circuit.
Control Circuit Description-
Certain other control components are available as “Optional“. When these optional components are installed with the
w
ater heater, the control circuit wiring diagram accordingly will include these components. The optional equipment
available from the manufacturer includes the following:
High Water Pressure Switch
Low Water Pressure Switch
Low Water Level Switch
Alarm Horn
Heating Element Sequencers
Electrical Door Lock
Control Circuit Wire Diagram
4
When the thermostat calls for heat, contacts close
inside the thermostat completing the circuit and
energizing the contactor coil.
The energized contactor coil causes the contactor to
close energizing the heating elements.
5
When the temperature setting of the thermostat is
reached, the contacts in the thermostat open. This
interrupts current flow through the control circuit de-
energizing the contactor coil.
6
The de-energized contactor coil causes the contactor
to open, interrupting current flow through the Heating
elements.
7
Page 10
NOTE: To help understand the concept of the operating sequence,
the control circuit shown is without any optional controls. See page
11 For control circuit showing all available optional controls
Control Circuit Sequence of Operation-
Line voltage from
power circuit
1
Line voltage is applied to control circuit fuse block.
2
Line voltage continues to transformer with one leg of
voltage connecting to the common terminal and the
other leg connecting to the appropriate line voltage
multi-tap terminal. Transformer output (always 120
volts) continues to high limit (ECO) control.
3
Hi limit (ECO) control is closed so one leg of 120 volts
continues to one side of the contactor coil. The other
leg is connected to the thermostat.
Appropriate line